Electric Boiler Use Excess Power implementation
Electric Boiler Use Excess Power Test System Model implementation - title
Electric Boiler Use Excess Power Test System Model Implementation
Electric Boiler Use Excess Power Test System Model implementation - overview
Test System Model Implementation Overview
Author / organization: Benedikt Leitner / AIT
Implemented Component Models / Implementation Tool:
- Electric Heater Implementation / Modelica
- Thermal Energy Storage Implementation / Modelica
Implementation Approach: Monolithic
Test Parameters of Test System Model : All parameters according to system configuration
Outputs/Measured Parameters:
- External electric grid:
- Power flows to and from
- Base district heating boiler
- heat generation
- District heating network
- Supply temperatures at substations
- Differential pressures at substations
- Low voltage distribution network
- Voltages at consumer connection points
- Transformer loading
Initial State of Test System Model:
- District heating pipes have nominal temperatures
- Thermal storages are empty, i.e., have nominal return temperature of district heating network
- Electric boilers not running
Temporal Resolution:
- District heating and electric boilers:
- dynamic, variable step size
- Electric network and model predictive controllers:
- 15 minutes
Related System Configuration
SmartDorf System Configuration
Related Test Case
Related Use Case
Electric Boiler Use Excess Power - description
Short Description
This test system model is used to verify that self-consumption of renewable energy sources in a coupled heat and power network improved using distributed power-to-heat appliances compared to a base scenario without power-to-heat. This means that energy flows flowing out of the network are reduced. At the same time energy imports should not increase. Relevant effort variables of both networks, i.e., bus voltages, supply temperatures and differential pressures, must stay within the allowable range. Also, the loading of the transformer is not allowed to reach critical levels. Otherwise the test fails.
Electric boilers are used as power-to-heat appliances. They consist of an electric heater, for the conversation of power to heat, and a thermal energy storage, for the (short-term) storage of generated heat. To plan the operation of the storage unit and the electric heater, a model predictive controller is used. The aim of the controller is to minimize negative residual load of the electric network. To enable this planning, negative residual load in the electric as well as heat demand in the heat network need to be known/predicted. This test assumes perfect knowledge of these time-series data and, thus, does not focus on the quality of predictions.
Media Gallery


Electric Boiler Use Excess Power Test System Model implementation - code
Source Code of the Implemented Result Object
Please contact:
Name: Benedikt Leitner / AIT